Tomasi, Roberta (2012) Energy performance, comfort and ventilation effectiveness of radiant systems coupled with mechanical ventilation. [Ph.D. thesis]

Questa è la versione più aggiornata di questo documento.

Full text disponibile come:

[img]
Preview
PDF Document
13Mb

Abstract (english)

This work presents the results of different numerical and experimental studies about energy performance, thermal comfort and ventilation effectiveness of radiant systems combined with different types of mechanical ventilation. Experimental studies have been carried out in Italy, in a test room in the laboratories of the company RHOSS S.p.A in Codroipo (Udine) and in Denmark, in a test room in the laboratories of the International Centre for Indoor Environment and Energy (ICIEE), at DTU (Danish Technical University), in Lyngby.
Radiant systems in residential and in office buildings are increasingly used because of the low heating or cooling demand and, at the same time, for the good thermal comfort they assure.
The thermal output estimation of radiant system in steady state condition needs the determination of the convective heat transfer coefficient from the surface to the room; a critical review among the correlations available in literature have been carried out and correlations for heated ceiling and cooled floor have been presented. Furthermore the variation of convective heat transfer coefficients, depending on the considered ventilation systems, has been estimated by means of the Computational Fluid Dynamics (CFD) technique.
The energy performance and thermal behavior of radiant systems during transient conditions have been predicted by using experimental tests and numerical calculations with the software Digithon that was developed by the University of Padua. In this work the validation of this software by comparison with experimental data has been presented.
In new and renovated buildings the high tightness and high insulation determine a potential risk of poor indoor air quality and condensation at the surfaces; for this reason an efficient ventilation system is necessary to provide for fresh air in the rooms. In a low polluted building air quality depends on human bioeffluents, among which carbon dioxide is considered the most significant one. By using numerical simulations (CFD) the effects of the supply and extract air terminals on contaminants distribution in offices equipped with a cooled ceiling has been investigated. Besides, in order to fully characterize the indoor climate of residential rooms or offices, an extensive experimental study has been carried out in a test room to determine both thermal comfort and ventilation effectiveness for different solutions of mixing ventilation and displacement ventilation combined with floor radiant systems. In particular, the effects of supply and extract air terminals positions by using low air change rates in mixing ventilation and the effects of different ventilation rates with displacement ventilations terminals have been analyzed. Results from experiments have been used for the validation of a CFD model for the prediction of air distribution in rooms equipped with mixed or displacement ventilation, combined with heating/cooling floor systems.

Abstract (italian)

In questo lavoro di dottorato vengono presentati i risultati di uno studio sui sistemi radianti per il raffrescamento ed il riscaldamento in ambito civile e sulla loro integrazione con opportuni sistemi di ventilazione meccanica. Le prestazioni energetiche in regime stazionario e transitorio, così come le prestazioni di comfort termico e di qualità dell’aria garantita, sono state studiate mediante l’ausilio di prove sperimentali, di simulazioni fluidodinamiche e di altri codici di calcolo.
Gli studi sperimentali sono stati realizzati in parte in Italia, presso i laboratori dell’azienda RHOSS S.p.A di Codroipo (Udine), e in parte presso i laboratori dell’ICIEE (International Centre for Indoor Environment and Energy), dell’Università Tecnica di Danimarca, (DTU) a Lyngby (DK).
L’aspetto più rilevante di questo lavoro è legato alla sempre maggiore diffusione dei sistemi radianti come soluzione per il riscaldamento ed il raffrescamento di ambienti interni, in quanto combinano vantaggi energetici ad elevati livelli di comfort termico. Per ragioni dovute alla piccola differenza di temperatura tra l’ambiente e il fluido termovettore, i sistemi radianti si interfacciano molto bene con caldaie a condensazione, pompe di calore, sistemi free cooling, collettori solari e altre sorgenti rinnovabili e soluzioni ad alta efficienza energetica.
Il calcolo della resa termica di tali sistemi viene eseguito mediante le equazioni valide per la convezione in regime stazionario, come quelle fornite dalle norme Europee EN 1264 ed EN 15377. In letteratura esistono numerose correlazioni valide per il calcolo della potenza convettiva di superfici orizzontali e verticali e di superfici interne di stanze reali; le norme EN 1264 ed EN 15377 consigliano correlazioni diverse e lo stesso accade per codici si simulazione energetica degli edifici. Ad oggi non è disponibile una chiara definizione di coefficiente di scambio termico convettivo per i sistemi radianti, specialmente per quanto riguarda pavimenti freddi e soffitti caldi. Il primo obiettivo di questa tesi è stato di realizzare un’analisi critica delle correlazioni disponibili in letteratura adatte ai sistemi radianti e di proporre delle equazioni per ogni configurazione di riscaldamento o raffrescamento da soffitto, pavimento o parete.
In ambito residenziale il pavimento radiante rappresenta una delle soluzioni più richieste grazie all’elevato livello di comfort termico garantito; tuttavia, al fine di migliorare la qualità dell’aria e specialmente a causa della necessità di deumidificare l’aria in estate per evitare formazione di condensa, accanto al sistema radiante andrebbe installato un sistema di ventilazione meccanica.
L’aria primaria in estate è solitamente a temperatura più bassa della temperatura della stanza e dotata di una certa velocità; nel caso di immissione da bocchette installate vicino ad una superficie radiante, lo scambio convettivo potrebbe venire variato rispetto ad una soluzione senza ventilazione. Mediante uno studio con simulazioni fluidodinamiche CFD è stato possibile valutare l’incremento dello scambio convettivo da un soffitto freddo mediante lo sfruttamento di aria primaria.
I sistemi radianti, in particolare i sistemi a soffitto, rappresentano un’ottima soluzione per rimuovere i carichi termici degli uffici durante il periodo estivo, ma allo stesso tempo possono essere usati per il riscaldamento invernale degli stessi con buone prestazioni energetiche e di comfort termico. La differenza sostanziale è che durante la stagione invernale il sistema radiante si trova a lavorare prevalentemente in regime stazionario, mentre durante la stagione estiva i carichi esterni dovuti alla radiazione solare e all’escursione diurna, accompagnati da carichi interni dovuti all’occupazione umana, determinano condizioni piuttosto variabili durante la giornata. Il comportamento di sistemi radianti a regimi stazionari e transitori sono state studiate mediante prove in camera climatica; inoltre un modello di calcolo chiamato Digithon, sviluppato all’interno del Dipartimento di Fisica Tecnica dell’Università di Padova, è stato validato mediante un confronto con dati sperimentali. Seguendo un’opportuna procedura, riportata nella tesi, è stato possibile impostare dei profili di carico che simulano una tipica giornata estiva o invernale su una parete della stanza ed è stato studiato come il soffitto radiante reagisca per cercare di mantenere una certa temperatura di comfort nella stanza.
Al fine di mantenere una buona qualità dell’aria, evitare la formazione di condensa, ma anche per incrementare la capacità di raffrescamento quando richiesto, i sistemi radianti per gli uffici andrebbero sempre associati a sistemi di ventilazione meccanica. Accanto ai tradizionali sistemi a soffitto con ventilazione a miscelazione, le soluzioni con ventilazione a dislocamento accoppiate a sistemi a pavimento o a soffitto sono alternative di crescente interesse per gli uffici. In edifici dove sia bassa la quantità di inquinanti emessi dai materiali edili, dai mobili e dalle attrezzature, la quantità di bioeffluenti dagli occupanti, dei quali l’anidride carbonica CO2 è normalmente usata come principale indicatore, è determinante per la qualità dell’aria interna. La capacità di rimozione dei contaminanti e, parallelamente, la capacità di immettere aria pulita negli ambienti sono espresse dall’efficienza di ventilazione (ventilation effectiveness). Mediante simulazione fluidodinamiche CFD è stato possibile confrontare l’efficienza di rimozione dei contaminanti utilizzando diverse soluzioni di ventilazione a dislocamento piuttosto che soluzioni tradizionali a miscelazione.
La qualità di un ambiente interno andrebbe misurata in termini sia di comfort termico garantito all’occupante che di qualità dell’aria. Attraverso prove sperimentali in laboratorio, i principali indici di comfort termico e di efficienza di ventilazione sono stati determinati per diverse configurazioni di ventilazione a miscelazione e di ventilazione a dislocamento in ambienti rappresentativi di applicazioni residenziali o del terziario. I risultati sono stati in seguito utilizzati per effettuare una validazione di un modello fluidodinamico (CFD) creato per la previsione del movimento dell’aria in ambienti residenziali o uffici.

Statistiche Download - Aggiungi a RefWorks
EPrint type:Ph.D. thesis
Tutor:De Carli, Michele
Supervisor:Olesen, Bjarne W.
Ph.D. course:Ciclo 24 > Scuole 24 > INGEGNERIA INDUSTRIALE > FISICA TECNICA
Data di deposito della tesi:26 January 2012
Anno di Pubblicazione:26 January 2012
Key Words:sistemi radianti, ventilazione meccanica, comfort termico, efficienza di ventilazione, rendimento energetico, qualità dell'aria interna / radiant systems, mechanical ventilation, thermal comfort, ventilation effectiveness, energy performance, indoor air quality
Settori scientifico-disciplinari MIUR:Area 09 - Ingegneria industriale e dell'informazione > ING-IND/10 Fisica tecnica industriale
Struttura di riferimento:Dipartimenti > pre 2012 - Dipartimento di Fisica Tecnica
Codice ID:4541
Depositato il:30 Oct 2012 10:06
Simple Metadata
Full Metadata
EndNote Format

Bibliografia

I riferimenti della bibliografia possono essere cercati con Cerca la citazione di AIRE, copiando il titolo dell'articolo (o del libro) e la rivista (se presente) nei campi appositi di "Cerca la Citazione di AIRE".
Le url contenute in alcuni riferimenti sono raggiungibili cliccando sul link alla fine della citazione (Vai!) e tramite Google (Ricerca con Google). Il risultato dipende dalla formattazione della citazione.

Chapter 2): Cerca con Google

[1] UNI, EN 1264—1999. Floor heating - Systems and components - Definitions and symbols. Cerca con Google

[2] UNI EN 15377—2008. Heating systems in buildings - Design of embedded water based surface heating and cooling systems. Cerca con Google

[3] Khalifa, A J N. 2000. Natural convective heat transfer coefficient- a review II. Surfaces in two- and three-dimensional enclosures. Energy Conversion and Management, 42,(2000), pp. 505-517. Cerca con Google

[4] Olesen, B W, Michel, E, Bonnefoi, F, De Carli, M. 2000. Heat Exchange coefficient between floor surface and space by floor cooling-Theory or a Question of Definition. ASHREE Transactions,2000, 106. Cerca con Google

[5] McAdams, W H. Heat Transmission.1954. McGraw-Hill. Cerca con Google

[6] Min, T C, Schutrum, L F, Parmelee G V , Vouris, J D. 1956. Natural convection and radiation in a panel-heated room. Heating, Piping & Air conditioning, May 1956, pp. 153-160. Cerca con Google

[7] Kreith, F. Principles of Heat Transfer. 1965. Int. Textbook Co, pp 347-348. Cerca con Google

[8] Jakob, M. Heat Transfer. Wiley & Sons. 1949. Vol 1, pp. 534-539. Cerca con Google

[9] Schutrum, L F, Parmelee, G V, Humphereys, C M.1953. Heat Exchanges in a Ceiling Panel Heated Room. 1953. ASHVE Transactions. Cerca con Google

[10] Khalifa, A J N, Marshall R H. Validation of heat transfer coefficients on interior building surfaces using a real-sized indoor test cell. Int. J. Heat Mass Transfer. Vol.33,(1998) No.10, pp.2219-2236. Cerca con Google

[11] Awbi, H B. 1998.Calculation of convective heat transfer coefficients of room surfaces for natural convection. Energy and Building. 28,(1998), pp. 219-227. Cerca con Google

[12] Awbi, H B. 1999. Natural convection from heated room surfaces. Energy and Buildings, 30 (1999), pp 233-244. Cerca con Google

[13] Karadağ, R. 2009. New approach relevant to total heat transfer coefficient including the effect of radiation and convection at the ceiling in a cooled ceiling room. Applied Thermal Engineering.29 (2009) pp.1561-1565. Cerca con Google

[14] Fohanno S, Polidori G. 2006 .Modelling of natural convective heat transfer at an internal surface. Energy and Buildings. 38, (2006). pp. 548-553. Cerca con Google

[15] Causone F, Corgnati, S , Filippi, M, Olesen B W. 2009. Experimental evaluation of the heat transfer coefficients between radiant ceiling and room. Energy and Buildings. 41,(2009) pp. 622-628. Cerca con Google

[16] ISO 7730 – 2005. Ergonomics of the thermal environment - Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria. Cerca con Google

[17] Klein, SA, Beckman, WA, Mitchel, JW et al. TRNSYS 15 Manual, University of Wisconsin.2002. Cerca con Google

[18] Klein, S.A., TRNSYS 16 Program Manual.SEL, University of Wisconsin, Madison USA. 2007. Cerca con Google

[19] EnergyPlus Engineering Reference October 2010. Cerca con Google

[20] Walton, G. N. 1983. Thermal Analysis Research Program Reference Manual. NBSSIR 83-2655. National Bureau of Standards. Cerca con Google

Chapter 3): Cerca con Google

[1] EN 14240- 2004. Ventilation for buildings - Chilled ceilings - Testing and rating. Cerca con Google

[2] ISO 7726-1998, Ergonomics of the thermal environment- Instrument for measuring physical quantities. Cerca con Google

[3] JCGM-2008. (GUM 1995 with minus corrections).Evaluation of measurement data- guide to the expression of uncertainty in measurement. Cerca con Google

[4] ENV 13005-1999. Guide to expression of uncertainty in measurement. Cerca con Google

[5] SIT/Tec-002/01. November 2001. Linee guida per la taratura dei misuratori di temperatura . SIT- Servizio di taratura in Italia (Italian National calibration service). Cerca con Google

[6] EA 4/02. December 1999. Expression of uncertainty of measurement in calibration. European co-operation for accreditation. Cerca con Google

[7] IEC 60751 -2008. Ed.2. Industrial platinum resistance thermometers and platinum temperature sensors. Cerca con Google

[8] IEC 60584-2- 1982. Ed. 1.Thermocouples. Part 2: Tolerances. Cerca con Google

Chapter 4): Cerca con Google

[1] Shoemaker, R. W. 1954. Le chauffage par rayonnement. Editions Eyrolles, Paris. Cerca con Google

[2] Olesen, B.W. 1997. Possibilities and Limitations of Radiant Floor cooling. ASHRAE Transactions 103 (1997), Pt.1. Cerca con Google

[3] Weber, T., Jóhannesson, G., Koschenz, M. , Lehmann, B., Baumgartner, T. 2005. Validation of a FEM-program (frequency-domain) and a simplified RC-model (time-domain) for thermally activated building component systems (TABS) using measurement data. Cerca con Google

[4] De Carli, M., Tonon, M. 2011. Effect of modelling solar radiation on the cooling performance of radiant floors. Solar Energy 85 (2011). pp. 689–712. Cerca con Google

[5] Athienitis, A. K., Chen, Y. 2000. The effect of solar radiation on dynamic thermal performance of floor heating systems. Solar Energy 69 (2000), No. 3, pp. 229–237. Cerca con Google

[6] Berglund, L. G., Gagge, A. P. 1985. Human response to thermal conditions maintained in an office by radiant ceiling, baseboard, forced air and floor heating systems. ASHRAE Transactions 91 (1985). pp. 488 - 502. Cerca con Google

[7] Külpmann, R. W. 1993. Thermal comfort and air quality in rooms with cooled ceilings - results of scientific investigations. ASHRAE Transactions, 99 (2) (1993),. pp. 488 - 502. Cerca con Google

[8] Fisher, D. E., Pedersen, C. O. 1997. Convective heat transfer in building energy and load calculation, ASHRAE Transactions 103 (2) (1997). Cerca con Google

[9] Khalifa, A. J. N., Marshall, R. H. 1998. Validation of heat transfer coefficients on interior building surfaces using a real-sized indoor test cell. Int. J. Heat Mass Transfer .33 (1998) No.10, pp.2219-2236. Cerca con Google

[10] De Carli, M., Tomasi, R. 2009. A critical review on heat exchange coefficients between heated and cooled horizontal surfaces and room. 11th Roomvent 2009 Conference, May 2009, Korea. Cerca con Google

[11] Stephenson, D. G., Mitalas, G. P. 1967. Cooling load calculation by thermal response factor method, ASHRAE Transactions 73 (1967). Cerca con Google

[12] Kusuda, T. 1969. Thermal response factors for multi-layer structures of various heat conduction systems. ASHRAE semi-annual Meeting, 1969, Chicago, IL. Cerca con Google

[13] Blomberg, T. 1999. Heat2 – A PC-program for heat transfer in two dimensions. Manual with brief theory and examples, Lund Group for Computational Building Physics, Sweden. Cerca con Google

[14] Various Authors. 1983. Fluid Mechanics and Heat Transfer. Hemisphere Publishing Corporation, 1983, cap. 2.5.1-1. Cerca con Google

[15] Awbi, H B. 1998. Calculation of convective heat transfer coefficients of room surfaces for natural convection. Energy and Building 28 (1998), pp. 219-227. Cerca con Google

[16] Olesen, B. W., Michel, E., Bonnefoi, F., De Carli, M. 2000. Heat Exchange coefficient between floor surface and space by floor cooling - Theory or a Question of Definition. ASHREE Transactions 106 (2000). Cerca con Google

[17] Karadağ, R. 2009. New approach relevant to total heat transfer coefficient including the effect of radiation and convection at the ceiling in a cooled ceiling room. Applied Thermal Engineering.29 (2009) pp.1561-1565. Cerca con Google

[18] EN 14240-2004. Ventilation for buildings - Chilled ceilings - Testing and rating. Cerca con Google

[19] ISO 7726-1998. Ergonomics of the thermal environment- Instrument for measuring physical quantities. Cerca con Google

[20] ENV 13005-1999. Guide to expression of uncertainty in measurement. Cerca con Google

[21] EnergyPlus Manual (Engineering Reference). U.S. Department of Energy, pp. 50-53. Cerca con Google

[22] EnergyPlus – Weather Data- U.S.Department of Energy. Cerca con Google

[23] F. P. Incropera,. D.P. DeWitt. 2002. Fundamentals of heat and mass Transfer, (5th Ed.), Wiley, New York. Cerca con Google

[24] ASTM. 2003. ASTM E779-03. Standard Test Method for Determining Air Leakage Rate by Fan Pressurization. Cerca con Google

[25] EN 1264-2008. Water based surface embedded heating and cooling systems. Cerca con Google

[26] EN 15377-2008. Heating systems in buildings - Design of embedded water based surface heating and cooling systems. Cerca con Google

Chapter 5): Cerca con Google

[1] Awbi, H.B., Hatton. 2000. A. Mixed convection from heated room surfaces. Energy and Buildings 32, (2000), pp. 153-166. Cerca con Google

[2] Jeong, J.W., Mumma, S.A. 2003. Ceiling radiant cooling panel capacity enhanced Cerca con Google

by mixed convection in mechanically ventilated spaces. Applied Thermal Engineering 23, pp. 2293–2306. Cerca con Google

[3] Beausoleil-Morrison, I. 2001.An algorithm for calculating convection coefficients for internal building surfaces for the case of mixed flow in rooms. Energy and Buildings 33, pp. 351-361 Cerca con Google

[4] Churchill, S.W., Usagi, R. 1972. A general expression for the correlation of rates of transfer and other phenomena. AIChE Journal 18 (6) (1972), pp. 1121-1128. Cerca con Google

[5] Alamdari, F., Hammond, G.P. 1983. Improved data correlations for buoyancy-driven convection in rooms, Building Services Engineering Research and Technology 4 (3) (1983), pp.106-112. Cerca con Google

[6] Fisher, D.E. 1995. An experimental investigation of mixed convection heat transfer in a rectangular enclosure, Ph.D. Thesis, University of Illinois, Urbana, USA. Cerca con Google

[7] Novoselac, A., Burley B.J., Sbrebric, J. 2006. New convection correlations for cooled ceiling panels in room with mixed and stratified airflow, HVAC&R RESEARCH, Volume 12, Number 2, pp. 279-294. Cerca con Google

[8] McGrattan, K. B., Klein, B., Hostikka, S. and Floyd, J. E. 2007. Fire Dynamics Simulator (Version 5), User’s Guide, NIST Special Publication 1019-5, National Institute of Standards and Technology, Building and Fire Research Laboratory, Gaithersburg, Maryland, USA. Cerca con Google

[9] A. Musser, K. McGrattan, J. Palmer, Evaluation of a fast, simplified, Computational Fluid Dynamic Model for solving Room Airflow Model, NISTIR 6760, NIST, 2001. Cerca con Google

[10] EN 12792 -2003. Ventilation for buildings - Symbols, terminology and graphical symbols. Cerca con Google

Chapter 6): Cerca con Google

[1] Toftum, J, Langkilde, G and Fanger, P O. 2004. New indoor environment chambers and field experiment offices for research on human comfort, health and productivity at moderate energy expenditure. Energy and Buildings 36, pp: 899–903 Cerca con Google

[2] Tanabe, S., E. Arens, F. Bauman, H. Zhang, and T. Madsen. et al. , 1994. Evaluating thermal environments by using a thermal manikin with controlled skin surface temperature. ASHRAE Transactions, Vol. 100, Pt. 1, pp. 39-48. Cerca con Google

[3] Causone, F., Baldin F., Olesen B.W., Corgnati, S.P. 2010 Floor heating and cooling combined with displacement ventilation: Possibilities and limitations. Energy and Buildings 42 (2010) 2338–2352. Cerca con Google

[4] Olesen, B.W., Babiak, J., Simone, A. 2007. How to measure operative temperature for control of radiant heating and cooling systems. Proceedings of Clima 2007,Helsinky, Finland. Cerca con Google

[5] Skistad, H. 1994, Displacement ventilation. Research Studies Press, John Wiley & Sons, Ltd., west Sussex. UK. Cerca con Google

[6] EN 15377-2008.Heating systems in buildings. Design of embedded water based surface heating and cooling systems. Cerca con Google

[7] Baldin , F. 2008. An experimental study of comfort and air distribution in a room with radiant floor heating/cooling and displacement ventilation. Master Thesis Cerca con Google

[8] Zerpellon, F. 2009. Experimental Study of Air Flow Patterns in a Space with Radiant and Convective Heating / Cooling Systems. Master thesis Cerca con Google

[9] EN 15251-2007. Indoor environmental input parameters for design and assessment of energy performance of buildings-addressing indoor air quality, thermal environment, lighting and acoustics. CEN, Brussels Cerca con Google

[10] Krajčík, M, Simone, A, Bjarne, W.O., Petršás, D. Experimental evaluation of thermal environment and ventilation effectiveness in a room heated by warm air. Indoor air Conference Texas 2011 Cerca con Google

[11] ISO 7730-2005. Ergonomics of the thermal environment — Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria Cerca con Google

[12] ISO 7726-1998. Ergonomics of the thermal environment-Instruments for measuring physical quantities Cerca con Google

[13] Fanger, P. O. Thermal Comfort, Danish Technical Press, 1970. Cerca con Google

[14] Matsunaga K, Sudo F, Tanabe S-I, Madsen. Evaluation and Measurement of Thermal Comfort in the Vehicles With a New Thermal Manikin. Sae Technical Paper Series 931958 (1663) 339-403 Cerca con Google

[15] Manikin Manual. Version 3.1 for Windows August 2008 (http://www.byteline.dk) Vai! Cerca con Google

[16] ASHRAE 1332-RP Revision to the ASHRAE thermal comfort tool to maintain consistency with Standard 55-2004. Final report 2006. Cerca con Google

[17] ASHRAE. 2004, Standard 55-2004: Thermal Environmental Conditions for Human Occupancy. Atlanta: American Society of Heating, Refrigeration, and Air-Conditioning Engineers Cerca con Google

[18] RHEVA Guidebook n°2. 2004.Ventilation effectiveness Cerca con Google

[19] Manual for application software 7620- LumaSense Technologies A/S Cerca con Google

Chapter 7): Cerca con Google

[1] Wargocki, P, Wyon, D. P., Baik, Y. K Fanger, P O. 2000. Productivity is affected by air quality in offices. Proceedings of Healthy Buildings 2000, Vol.1, pp 635-640. Cerca con Google

[2] Wargocki, P, Wyon, D. P., Sundell, J., Clausen, G., Fanger, P. O. 2000. The Effects of Outdoor Air Supply Rate in a Office on Perceived Air Quality, Sick Building Syndrome (SBS) Symptoms and Productivity. Indoor Air 2000 (10), pp 222-226. Cerca con Google

[3] CEN report CR 1752-1998. Ventilation for buildings - design criteria for the indoor environment. CEN/TC 156/WG 6. Cerca con Google

[4] De Gids, W.F., Wouters, P. 2010. CO2 as indicator for the indoor air quality - general principles. AIVC.VIP N°33 July2010. Cerca con Google

[5] Persily, A.K., 1996.The relationship between indoor air quality and carbon dioxide, Proceedings of Indoor Air 1996, Nagoya, Japan, Vol. 2, pp 992-996. Cerca con Google

[6] EN 15251-2007. Indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality, thermal environment, lighting and acoustics. Cerca con Google

[7] Mundt et al., RHEVA Guidebook n°2. 2004.Ventilation effectiveness. Cerca con Google

[8] Hirnikel, D.J; Lipowicz, P.J.; Lau, R.W. Predicting contaminant removal effectiveness of three air distribution systems by CFD modeling. 2002. ASHRAE Transactions, Vol. 108, part 1, pp 350-359. Cerca con Google

[9] Lin, Z., Chow, T.T., Tzang. C.F., Fong. K.F., Chan. L.S.2005.CFD study on effect of the air supply location on the performance of the displacement ventilation system. Building and Environment 40 (2005), pp 1051-1067. Cerca con Google

[10] Novoselac, A., Sbrebric, J. 2002. A critical review on the performance and design of combined cooled ceiling and displacement ventilation systems. Energy and Buildings 34 (2002), pp 497-509. Cerca con Google

[11] ISO 7730:2005. Ergonomics of the thermal environment — Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria. Cerca con Google

[12] ASTM D6245-98 -2002. Standard guide for using indoor carbon dioxide concentrations to evaluate indoor air. Cerca con Google

[13] Kobayashi, N. and Chen, Q. 2003. Floor-supply displacement ventilation in a small office. Cerca con Google

Indoor and Built Environment, 12(4), 281-292. Cerca con Google

Chapter 8): Cerca con Google

[1] Nielsen, P.V. 1973. Berechnung der Lufbewegung in einem zwangsbelüfteten Raum, Gesundheits-Ingenieur. Cerca con Google

[2] Catalina, T., Virgone, J., Kuznik, F. 2009.Evaluation of thermal comfort using combined CFD and experimentation study in a test room equipped with a cooling ceiling . Building and Environment 44 (2009) 1740–1750. Cerca con Google

[3] Causone, F. , Olesen, B.W., Corgnati, S.P. 2010. Floor Heating with Displacement Ventilation: Cerca con Google

An Experimental and Numerical Analysis, HVAC&R RESEARCH, Vol. 16 n°2, 2010 Cerca con Google

[4] McGrattan, K. et al., Fire Dynamic Simulator (version 5), Technical Reference Guide, NIST special publication 1018-5, 2010. Cerca con Google

[5] De Carli, M., Scarpa, M., Tomasi, R., Villi, G. 2011. Evaluation of radiant system performance enhancement by means of primary air. Roomvent 2011 Conference, Trondheim, Norway. Cerca con Google

[ Cerca con Google

[6] Musser, A., McGrattan, K., Palmer, J. Evaluation of a fast, simplified, Computational Fluid Dynamic Model for solving Room Airflow Model, NISTIR 6760, NIST, 2001. Cerca con Google

[7] EN 15251. 2007. Indoor environmental input parameters for design and assessment of energy performance of buildings-addressing indoor air quality, thermal environment, lighting and acoustics. CEN, Brussels. Cerca con Google

[8] Smagorinsky, J. 1963. General Circulation Experiments with the Primitive Equations. I. The Basic Experiment. Monthly Weather Review, 91(3):99–164, March 1963. Cerca con Google

[9] Zhang, W., Ryder, N., Roby, R.J, Carpenter. D. Modeling of the Combustion in Compartment Fires Using Large Eddy Simulation Approach. In Proceedings of the 2001 Fall Technical Meeting, Eastern States Section. Combustion Institute, Pittsburgh, Pennsylvania, December 2001. Cerca con Google

[10] Werner, H., Wengle, H.1991. Large-eddy simulation of turbulent flow over and around a cube in a plate channel. In 8th Symposium on Turbulent Shear Flows, pages 155–168, 1991. Cerca con Google

[11] Forney, G. P. Smokeview (Version 5) - A Tool for Visualizing Fire Dynamics Simulation Data Volume II: Technical Reference Guide. NIST special publication 1017-2, 2010. Cerca con Google

[12] Nielsen, P.V. et al., RHEVA Guidebook n°10. 2004. Computational Fluid Dynamics in ventilation design. Cerca con Google

[13] Gosman, A.D., Nielsen, P.V., Restivo, A., Whitelaw, J.H. 1980. The flow Properties of Rooms With small Ventilation Openings, Journal Of Fluid Engineering, (1980), Vol.102, pp.316-322. Cerca con Google

[14] ASHRAE 1997. Handbook of Fundamentals – SI Edition. American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. Atlanta, GA. Cerca con Google

[15] Olesen, B W, Michel, E., Bonnefoi, F, De Carli, M. 2000. Heat Exchange coefficient between floor surface and space by floor cooling-Theory or a Question of Definition. ASHREE Transactions 2000, 106 Pt.1 Cerca con Google

[16] ISO 7730:2005. Ergonomics of the thermal environment — Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria. Cerca con Google

[17] Sandberg, M. What is ventilation efficiency? Building and Environment, Vol. 19, n°2, pp. 123-135. Cerca con Google

[18] Mundt, E. et al. RHEVA Guidebook n°2. 2004.Ventilation effectiveness. Cerca con Google

[19] ASTM 1995. ASTM Standard E741-95. Test method for determining air change in a single zone by means of tracer gas dilution. Philadelpia: American Society for Testing and Material. Cerca con Google

Versioni disponibili di questo documento

Download statistics

Solo per lo Staff dell Archivio: Modifica questo record