Testa, Samuele (2013) Airflow fields analysis in bounded domains with CFD methods. [Ph.D. thesis]

Full text disponibile come:

[img]
Preview
PDF Document
6Mb

Abstract (english)

In the current work the focus is on natural ventilation occurring in buildings. The first step is to discuss the potential of numerical models applied to determine building performance and air flow as part of a mixed mode building control scheme with respect to a test case. A dynamic simulation software (TRNSYS) is used to estimate the annual energy demand. An optimization program (GenOpt) changes iteratively the parameters regulating the airflow within the building model in order to minimize the whole year energy use. Elements which are considered in the analysis are outdoor climatic conditions and elements representing the building use, such as internal gains. The numerical results of this analysis have shown how a proper analysis of natural ventilation phenomena occurring in small premises can lead to energy saving while thermal comfort is not compromised. This has been tested in various Italian climates, by means of tuning different parameters handling the natural ventilation in a mixed mode office room. The natural ventilation to be effective has to be carefully designed and it may not just occur. On the other hand in large enclosures such as atria or churches, where much more complicated phenomena occur in the indoor air flow, the natural ventilation is not so straightforward to analyse. This fact pushes the application of numerical methods capable of higher resolution in order to catch the features of the streams, with the aim of achieving good levels of thermal comfort and indoor air quality. In particular, in the last years a growing attention has been paid on the analysis of building airflow, mostly due to the diffuse interest in reducing energy losses and optimizing the efficiency of heating systems.
A nontrivial technical problem is the heating of churches, because nowadays they are used both for religious services and as cultural places. Such problem is still open and no solution has been so far found. In the course of the last century, with the installation of new heating systems, an increase in damage and the decay of valuable interior decoration have been noticed. Moreover in this kind of environments, because of the remarkable heights and the presence of great windows, relevant natural and mixed convection flows may show up and, on the other hand, stratification phenomena may occur, with hot air stagnation far from occupied zones. This can cause people discomfort or energy waste. Therefore it is not possible to design heating plants only to maximize energy efficiency, but the heating systems have to accomplish the best compromise between preservation of cultural property, economy, energy and comfort. For handling all these conflicting requirements at once, simplified or macroscopic models, which describe the real system only with a small number of temperature, pressure and flow rate values, are no more enough, but microclimate field flow models, based on computational fluid dynamics methods (CFD), provide a powerful and versatile tool to obtain a more reliable prediction of the air movement and temperature distribution within the built environment.
The case of St. Marien’s church has been investigated to prove the utility of this kind of analysis. On the basis of experimental data collected during winter 2003-2004, a thermal model of St. Marien church has been produced and tuned. The results provided by this model have been used in this work to perform several simulations on St. Marien church with the commercial CFD software FLUENT, in order to find out a computational model which could be a good compromise between simplicity on geometrical representation, saving on computational resources, accuracy and reliability of the solution. Once the model was set up, it has been validated against some temperature values recorded during the monitoring period. Simulations have highlighted a shortcut of the flow from the inlet to the outlet, giving the reason why energy model of the church tuned on the experimental data are overestimating energy consumption. This would not have been possible with a macroscopic analysis, showing the need for large enclosure to carry on both the analyses together.
This promising result pushed to test a more direct way to couple energy models and CFD models to predict energy consumptions in buildings or buildings components involving remarkable ventilation phenomena. It came out a method to estimate ventilated components performance on annual bases in a sensible amount of time. The method was applied to a ventilated roof. In this case the considered vented roof showed to increase energy saving with respect to the typical roof layout in climates with high solar radiation levels during a wide period of the year.







Abstract (italian)

Nel lavoro svolto in questa tesi l'attenzione è rivolta ai fenomeni di ventilazione naturale che avvengono negli edifici. Il primo studio ha riguardato il potenziale della modellazione numerica relativamente alle prestazioni dell'edificio come parte di uno schema di controllo della ventilazione mista in riferimento a un caso test. A tal fine è stato utilizzato un software di simulazione dinamica (TRNSYS) per valutare il fabbisogno annuale di energia accoppiato a un programma di ottimizzazione (GenOpt) in grado di modificare i parametri di interesse in maniera iterativa; i risultati dell’analisi hanno permesso di individuare la combinazione di parametri per cui il consumo energetico è minimo su base annuale.
Sono state considerate nell'analisi le condizioni climatiche e gli elementi rappresentativi del tipo di utilizzo dell'edificio come i carichi interni. Dai risultati numerici di questa analisi è stato possibile mostrare come un’analisi dettagliata della ventilazione naturale all’interno di ambienti di piccole dimensioni possa portare a un risparmio di energia senza compromettere il comfort termico. Questo è stato provato per diverse regioni climatiche, tarando i diversi parametri che gestiscono la ventilazione naturale nella stanza adibita a ufficio soggetta a ventilazione mista. Il lavoro ha dimostrato come la ventilazione naturale per essere efficiente debba essere pianificata a priori sia per definire le aperture sia per stabilirne la gestione.
D'altro canto, in ambienti interni di grandi dimensioni come atri o chiese, dove avvengono fenomeni molto più complessi nei campi di moto dell'aria, la ventilazione naturale non è così semplice da analizzare. Questo fatto spinge all'adozione di metodi caratterizzati da una maggiore risoluzione al fine di meglio definire le caratteristiche del deflusso, quando si studiando intende studiare il comfort termico e la qualità dell'aria. In particolare, negli ultimi anni, c'è stata una crescente attenzione riguardo allo studio dei campi di moto dell'aria all’interno degli edifici, dovuto al diffuso interesse nel ridurre le perdite di energia e a incrementare l'efficienza dei sistemi di riscaldamento. Un problema tecnico non banale riguarda il riscaldamento delle chiese, dal momento che queste oggi sono sempre più utilizzate sia per funzioni religiose che come centri culturali. Tale questione è tuttora aperta, non avendo ancora trovato una soluzione definitiva. Nel corso dell'ultimo secolo, a seguito dell'installazione dei sistemi di riscaldamento, si è manifestato un aumento di danni delle opere d’arte e delle preziose decorazioni all’interno delle chiese storiche. Inoltre in ambienti di questo tipo, a causa dell’accentuato sviluppo verticale e della presenza di grandi finestrature, si possono verificare importanti fenomeni di convezione naturale o fenomeni di stratificazione in cui l'aria calda tende a ristagnare in regioni lontane dalla zona occupata. Le conseguenze possono essere discomfort termico o spreco di energia. Pertanto non è possibile progettare impianti di riscaldamento secondo metodologie standard, quanto dal momento che gli impianti di riscaldamento devono realizzare il miglior compromesso fra conservazione dei beni culturali, costi di esercizio e di manutenzione, risparmio energetico e comfort. Per gestire queste esigenze spesso contrastanti, i modelli macroscopici o ingegneristici che descrivono il sistema reale con un numero ridotto di valori di temperatura, pressione e portata di massa, non sono molto spesso adeguati, mentre la fluidodinamica numerica è uno strumento potente e versatile per ottenere una previsione più affidabile del moto dell'aria e dei campi termici che avvengono negli edifici.
Dopo aver illustrato il problema del riscaldamento delle chiese storiche e i principi della CFD, si è condotta un'analisi dettagliata della chiesa di St.Marien a Wismar per dimostrare l'utilità di questi metodi per questo tipo di applicazioni. Sulla base dei dati sperimentali raccolti durante l'inverno 2003-2004, è stato realizzato e tarato un modello energetico dinamico della chiesa. I risultati forniti hanno permesso di stimare le condizioni al contorno per una serie di simulazioni della chiesa di St.Marien basate sul codice commerciale FLUENT, per identificare un modello numerico che potesse essere un buon compromesso fra semplicità del dominio spaziale di calcolo, risparmio di risorse di calcolo, accuratezza e affidabilità della soluzione. Una volta realizzato, il modello è stato validato con alcuni valori di temperatura registrati durante il periodo di monitoraggio. Le simulazioni hanno evidenziato la presenza un cortocircuito in corrispondenza a un fan-coil installato a pavimento.
Questo non sarebbe stato possibile con un'analisi basata su modelli semplificati, indicando la necessità, per i grandi ambienti, di portare avanti insieme sia le analisi macroscopiche che quelle di dettaglio con metodi CFD. Questo risultato ha spinto a provare in modo più stretto di accoppiare modelli energetici e CFD al fine di predire le prestazioni energetiche degli edifici. E’ stato quindi prodotto un metodo per stimare le prestazioni di componenti ventilati dell'involucro edilizio su base annuale. Il metodo è stato testato su un tetto ventilato. Si è quindi potuto verificare il miglior comportamento energetico del tetto ventilato rispetto a una equivalente copertura tradizionale.

Statistiche Download - Aggiungi a RefWorks
EPrint type:Ph.D. thesis
Tutor:De Carli, Michele
Ph.D. course:Ciclo 24 > Scuole 24 > INGEGNERIA INDUSTRIALE > ENERGETICA
Data di deposito della tesi:31 January 2013
Anno di Pubblicazione:31 January 2013
Key Words:CFD, Large enclosure, indoor, thermal comfort
Settori scientifico-disciplinari MIUR:Area 09 - Ingegneria industriale e dell'informazione > ING-IND/10 Fisica tecnica industriale
Struttura di riferimento:Dipartimenti > Dipartimento di Ingegneria Industriale
Codice ID:5948
Depositato il:14 Oct 2013 11:09
Simple Metadata
Full Metadata
EndNote Format

Bibliografia

I riferimenti della bibliografia possono essere cercati con Cerca la citazione di AIRE, copiando il titolo dell'articolo (o del libro) e la rivista (se presente) nei campi appositi di "Cerca la Citazione di AIRE".
Le url contenute in alcuni riferimenti sono raggiungibili cliccando sul link alla fine della citazione (Vai!) e tramite Google (Ricerca con Google). Il risultato dipende dalla formattazione della citazione.

1 References Cerca con Google

[1] 1998.Ventilation of Large Spaces in Buildings: Analysis and Prediction Techniques, Heiselberg P, Murakami S, Roulet C-A (editors), Denmark, Aalborg, Aalborg University, Cerca con Google

[2] Miao W., Chen Q., 2009.Assessment of Various Turbulence Models for Transitional Flows in an Enclosed Environment. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Cerca con Google

[3] Cable M., 2009. An Evaluation of Turbulence Models for the Numerical Study of Forced and Natural Convective Flow in Atria. Ph.D. Thesis, Queen's University Kingston, Ontario, Canada Cerca con Google

[4] Zuo W., Chen Q. ,2008. Real-time or faster-than-real-time simulation of air?ow in buildings. Indoor Air Cerca con Google

[5] Zhang T.T., Lee K., Chen Q., 2009. A simpli?ed approach to describe complex di?users in displacement ventilation for CFD simulations. Indoor Air Cerca con Google

[6] Koskela H., 2004. Momentum source model for CFD-simulation of nozzle duct air diffuser. Energy and Buildings. Cerca con Google

2 References Cerca con Google

[1] Allard, F. 1998. Natural ventilation in buildings. James & James Editor. Cerca con Google

[2] ASHRAE 2005. Fundamental Handbook. American Society of Heating, Refrigerating and Air-Conditioning Engineers Inc. Cerca con Google

[3] Chen, Q. 2009. Ventilation performance prediction for buildings: A method overview and recent applications. Building and Environment 44, pp. 848-858. Cerca con Google

[4] Costola, D., Alucci, M. 2007. Pressure coefficient simulated by CFD for wind-driven ventilation analysis. Proceedings of the 7th IBPSA Conference, Beijing, China, pp. 999–1006. Cerca con Google

[5] Daskalaki, E., Santamouris, M., Bruant, M., Balaras, C.A., Bossaer, A., Ducarme, D., Wouters, P. 1999. Modeling large openings with COMIS. Energy and Buildings 30, pp. 105-115. Cerca con Google

[6] Favarolo, D., Manz, H. 2005. Temperature-driven single-sided ventilation through a large rectangular opening. Building and Environment 40, pp. 689-699. Cerca con Google

[7] Klein S.A. et al. 2002. TRNSYS Manual. University of Wisconsin (USA). Cerca con Google

[8] Kolokotsa, D., Pouliezos, A., Stavrakakis, G., Lazos, C. 2009. Predictive control techniques for energy and indoor environmental quality management in buildings. Building and Environment 44, pp. 1850-1863. Cerca con Google

[9] Omer, AM. 2008. Renewable building energy systems and passive human comfort solutions. Renewable & Sustainable Energy Reviews 12, pp. 1562-1587. Cerca con Google

[10] Mahdavi, A. 2001. Simulation-based approach to natural ventilation. Building and Environment 36, pp. 789-796. Cerca con Google

[11] Mahdavi, A., Pröglhöf, C. 2008. A model-based approach to natural ventilation. Building and Environment 43, pp. 620-627. Cerca con Google

[12] McDowell, T.P. et al. 2003. Integration of airflow and energy simulation using CONTAM and TRNSYS. ASHRAE Transactions, Vol. 109, Part 2. Cerca con Google

[13] Spindler, H.C., Norford, L.K. 2009. Naturally ventilated and mixed-mode buildings - Part II: Optimal control. Building and Environment 44, pp. 750-761. Cerca con Google

[14] Walton, G.N. and Stuart Dols, W. 2006. CONTAM 2.4b User Guide and program Documentation, NISTIR 7251. National Institute of Standards and Technology, Gaithersburg (USA). Cerca con Google

[15] Wetter, M. 2001. GenOpt® Generic Optimization program. Proceedings of the 7th IBPSA Conference, Rio de Janeiro, Brazil, pp. 601–608. Cerca con Google

[16] Testa S., Villi G., De Carli M., 2009. Optimization of natural ventilation design with reference to building characteristics and outdoor climatic conditions by means of a multi objective cost function Cerca con Google

3 References Cerca con Google

[1] A. Boerstra, P. Op't Veld, H. Eijdems. “The health, safety and comfort advantages of low temperature heating systems: a literature review”. Healthy Buildings, Helsinki (SF), 6th-10th August 2000 Cerca con Google

[2] A. Dumas, G. Barozzi, S. Anzillotti, P. Proli, “La chiesa di S. Maria della Pietà di Bologna”, Conference for Lorenzo Agnolotto, 26th June 2003, Udine (I). Cerca con Google

[3] M. A. Corticelli, A. Muscio, P. Tartarini, “Analisi CFD dei campi di moto e di temperatura dell’aria in una cattedrale”, 58th ATI National Conference, September 2003, San Martino di Castrozza (I) Cerca con Google

[4] http://www.lowex.net/english/inside/material.html, Lowex news n.° 6. Vai! Cerca con Google

[5] S. Facco, “Comportamento termico dei grandi ambienti riscaldati tramite moduli radianti a gas”, Master thesis 2001-2002, IUAV University of Architecture of Venice (Italy). Cerca con Google

[6] A.Troi, G. Hausladen, “Heating effects in South Tyrolean churches”, Indoor Air 2002, Monterey (USA). Cerca con Google

[7] Pillepich R., 2004. CFD MODELLING OF HISTORICAL CHURCHES FOR HEATING OPTIMIZATION Cerca con Google

4 References Cerca con Google

[1] Ansys Fluent 12.0 12.1 Documentation Cerca con Google

[2] Versteeg H. K., Malalasekera W., 2007. An Introduction to Computational Fluid Dynamics, The Finite Volume Method, second edition. Pearson Education Limited Cerca con Google

[3] Jasak H., Weller H.G., Gosman A.D., 1999. High resolution NVD differencing scheme for arbitrarily unstructured meshes. International journal for numerical methods in fluids Cerca con Google

[4] s. V. Patankar and d. B. Spalding, 1972. Calculation momentum procedure transfer for heat, mass and in three-dimensional parabolic flows. Int. J. Heat Mass Transfer Vol. IS, pp. 1787-1806. Cerca con Google

[5] Wilcox David C, 1998. Turbulence Modeling for CFD. Second edition. Anaheim: DCW Industries. Cerca con Google

[6] Bredberg J. 2001.On Two-equation Eddy-Viscosity Models. Internal Report 01/8, Department of Thermo and Fluid Dynamics Chalmers University Of Technology Cerca con Google

[7] Bredberg J. 2000. On the Wall Boundary Condition for Turbulence Models. Internal Report 00/4, Department of Thermo and Fluid Dynamics Chalmers University Of Technology Cerca con Google

[8] Issa R. I., 1985. Solution of the Implicitly Discretized Fluid Flow Equations by Operator-Splitting, Journal of Computational Physics, 62, pp 40-65. Cerca con Google

[9] Issa R. I., Gosman A. D., Watkins A. P., 1986. The Computation of Compressible and Incompressible Recirculating Flow by a Non-Iterative Implicit Scheme, Journal of Computational Physics, 62, pp 66-82. Cerca con Google

[10] Oliveira P. J., Issa R. I., 2001. An Improved PISO Algorithm for the Computation of Buoyancy-Driven Flows, Numerical Heat Transfer, Part B, 40, pp 473-493. Cerca con Google

[11] Zuo W., Chen Q. ,2008. Real-time or faster-than-real-time simulation of air?ow in buildings. Indoor Air Cerca con Google

5 References Cerca con Google

[1] Srebric, J., Chen, Q. 2002 An example of verification, validation, and reporting of indoor environment CFD analyses , ASHRAE Transactions 2002;108(2):185–94 Cerca con Google

[2] Launder, B.E., Spalding, D.B. 1974 The Numerical Computation of Turbulent Flow., Computer Methods in Applied Mechanics and Engineering, 3:269-289, 1974. Cerca con Google

[3] Wilcox, D. C. 1998 Turbulence Modeling for CFD, DCW Industries, Inc., La Canada, California Cerca con Google

[4] Hagström, K., Sandberg, E., Koskela, H., Hautalampi T. 2000 Classification for the room air conditioning strategies, Building and Environment 35 (2000) 699-707 Cerca con Google

[5] Sørensen, D. N., Nielsen, P. V. 2003 Quality control of computational fluid dynamics in indoor environments, Indoor Air, 13, 2-17 Cerca con Google

[6] Testa S., De Carli M., Olesen B. W., Heimsch R., 2011. Effect of geometry on flow field and temperature distribution in large indoor environments. Roomvent 2011 Cerca con Google

[7] Ansys Fluent 12.0 12.1 Documentation Cerca con Google

[8]Pillepich R., 2004. CFD MODELLING OF HISTORICAL CHURCHES FOR HEATING OPTIMIZATION  Cerca con Google

6 References Cerca con Google

[1] UNI, EN 1264—1999. Floor heating - Systems and components - Definitions and symbols. Cerca con Google

[2] UNI EN 15377—2008. Heating systems in buildings - Design of embedded water based surface heating and cooling systems. Cerca con Google

[3] Khalifa, A J N. 2000. Natural convective heat transfer coefficient- a review II. Surfaces in two- and three-dimensional enclosures. Energy Conversion and Management, 42,(2000), pp. 505-517. Cerca con Google

[4] Olesen, B W, Michel, E, Bonnefoi, F, De Carli, M. 2000. Heat Exchange coefficient between floor surface and space by floor cooling-Theory or a Question of Definition. ASHREE Transactions,2000, 106. Cerca con Google

[5] McAdams, W H. Heat Transmission.1954. McGraw-Hill. Cerca con Google

[6] Min, T C, Schutrum, L F, Parmelee G V , Vouris, J D. 1956. Natural convection and radiation in a panel-heated room. Heating, Piping & Air conditioning, May 1956, pp. 153-160. Cerca con Google

[7] Kreith, F. Principles of Heat Transfer. 1965. Int. Textbook Co, pp 347-348. Cerca con Google

[8] Jakob, M. Heat Transfer. Wiley & Sons. 1949. Vol 1, pp. 534-539. Cerca con Google

[9] Schutrum, L F, Parmelee, G V, Humphereys, C M.1953. Heat Exchanges in a Ceiling Panel Heated Room. 1953. ASHVE Transactions. Cerca con Google

[10] Khalifa, A J N, Marshall R H. Validation of heat transfer coefficients on interior building surfaces using a real-sized indoor test cell. Int. J. Heat Mass Transfer. Vol.33,(1998) No.10, pp.2219-2236. Cerca con Google

[11] Awbi, H B. 1998.Calculation of convective heat transfer coefficients of room surfaces for natural convection. Energy and Building. 28,(1998), pp. 219-227. Cerca con Google

[12] Awbi, H B. 1999. Natural convection from heated room surfaces. Energy and Buildings, 30 (1999), pp 233-244. Cerca con Google

[13] Karadag, R. 2009. New approach relevant to total heat transfer coefficient including the effect of radiation and convection at the ceiling in a cooled ceiling room. Applied Thermal Engineering.29 (2009) pp.1561-1565. Cerca con Google

[14] Fohanno S, Polidori G. 2006 .Modelling of natural convective heat transfer at an internal surface. Energy and Buildings. 38, (2006). pp. 548-553. Cerca con Google

[15] Causone F, Corgnati, S , Filippi, M, Olesen B W. 2009. Experimental evaluation of the heat transfer coefficients between radiant ceiling and room. Energy and Buildings. 41,(2009) pp. 622-628. Cerca con Google

[16] ISO 7730 – 2005. Ergonomics of the thermal environment -- Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria. Cerca con Google

[17] Klein, SA, Beckman, WA, Mitchel, JW et al. TRNSYS 15 Manual, University of Wisconsin.2002. Cerca con Google

[18] Klein, S.A., TRNSYS 16 Program Manual.SEL, University of Wisconsin, Madison USA. 2007. Cerca con Google

[19] EnergyPlus Engineering Reference October 2010. Cerca con Google

[20] Walton, G. N. 1983. Thermal Analysis Research Program Reference Manual. NBSSIR 83-2655. National Bureau of Standards. Cerca con Google

[21] Villi G., Pasut W., Testa S., De Carli M., 2010. Analisi prestazionale comparativa tra copertura ventilata e tradizionale in regime estivo. 65° Congresso Nazionale ATI. Cerca con Google

[22] Versteeg H. K., Malalasekera W., 2007. An Introduction to Computational Fluid Dynamics, The Finite Volume Method, second edition. Pearson Education Limited Cerca con Google

7 References Cerca con Google

[1] Deitel H. M., Deitel P. J., 2005. C++ How to Program, Fifth Edition. Prentience Hall, Inc. Cerca con Google

[2] Wang M.; Chen Q., 2009. Assessment of Various Turbulence Models for Transitional Flows in an Enclosed Environment, HVAC&R Research;Nov2009, Vol. 15 Issue 6, p1099 Cerca con Google

[3] 2011. OpenFOAM the open source CFD toolbox: User Guide, Version 2.0.0 Cerca con Google

[4] Jayatilleke. C., 1969.The Influence of Prandtl Number and Surface Roughness on the Resistance of the Laminar Sublayer to Momentum and Heat Transfer. Prog. Heat Mass Transfer, 1:193-321. Cerca con Google

[5] Weller H. G.,. Tabor G, 1998. A tensorial approach to computational continuum mechanics usingobject-oriented techniques COMPUTERS IN PHYSICS, VOL. 12, NO. 6, NOV/DEC 1998 Cerca con Google

Download statistics

Solo per lo Staff dell Archivio: Modifica questo record